A and B feeds

Two independent power paths to each rack, so equipment with two power supplies keeps running if one path fails.

Also: dual-corded, dual feed, A/B power

Most servers and switches have two power supplies. In a dual-fed design, each rack gets an A feed and a B feed from separate PDUs, UPS systems and switchgear, and each device plugs one supply into each. If either path fails or is shut for maintenance, the other carries the full load. This only works if each feed is kept below half its rating in normal running, so that it can take everything if needed.